Bulk Cables  |  Control wire (LIY-CY)

flexible, EMC- overall copper braiding in compliance with DIN 47100, self-extinguishing and flame-retardant in compliance with CEI20-22II (Test Type B)



SOMMER CABLE - SC-CONTROL FLEX



mobilestudioinstallationELA

analogFRNCOFC



Who wants to pay taxes...

but in this case an exception just has to be made. To understand that German “joke“ you need to know that “tax“ and “control“ both are translated with “Steuer“. We supply a robust and yet very flexible control cable, which is used as a signal cable for the milliampere range on control units (e.g. RS232 and RS422) and computer systems. This special jacket is self-extinguishing and flame-retardant in compliance with VDE 0472, Part 804, Test Type B.
The CONTROL FLEX is rounded off with shielding made of copper braiding (opt. cover > 90 %). This makes it especially suitable for EMCproblem applications. Please note: as we also produce this cable for wholesalers of electrical equipment and OEM customers, it is usually only available with the DIN-imprint or other approbation, i.e. without the SOMMER CABLE logo.

THE ADVANTAGES:

  • Available and in stock in seven different wire diameters
  • Remains flexible in moving condition to 14 °F (fixed installation -22 °F)
  • Largely oil-resistant
  • Self-extinguishing and flame-retardant in compliance with VDE 0472, Part 804, Test Type B
  • Very easy to work with


THE APPLICATION:

  • Fixed installation in building technology
  • Signal wire for control technology
  • Transmission of RS232- and RS422-standards
  • Speaker cable for ELA-technology



TECHNICAL DATA:
ConstructionLIY-CY
Jacket, diameter7,20 mm
No. of inner conductors6 x 0,50 mm2
Copper strand per conductoraccording to DIN VDE 0295 mm
Conductor insulationPVC/FRNC according to DIN VDE0207 part 4
Shieldingcopper braiding, tin-plated
Shielding factor90 %
Temperature rangeFixed installation min. -30 °C
Temperature rangeMobile min. -20 °C
Temperature rangeFixed installation max. 80 °C
Temperature rangeMobile max. 70 °C
Jacket colorgray (RAL 7001)
Packaging100/1000 m roll

ELECTRICAL DATA:
Capac. cond./cond. per 1 m120 pF
Capac. cond./shield. per 1 m240 pF
Cond. resistance per 1 km< 165 Ohm
Insulat. resistance per 1 km> 20 MOhm
Inductance at 1 km0,65 MHz
Operation voltage
Operation voltage
Test voltageat 50 Hz (cond./cond.) 1200 V
Test voltageat 50 Hz (cond./shield.) 800 V

ORDER DATA:
Order No.380-0056-06050
Rec. priceon request



v2010-JUN-14